Cooling Tower Chemicals
From ChemWorld. We sell direct to all End users. No order to small.
The purpose of cooling tower chemicals are to prevent scale, minimize corrosion, and reduce bacteria. The ultimate goal is to reduce water usage, save on energy and to extend equipment life. All chemicals listed here are design to do that. Depending if you have surface, ground, or city water will effect the type of chemical you need. Please do not hesitate to call us if you have additional questions.
Our goal with ChemWorld is to make your chemical purchasing needs Easy to Find, Easy to Remember, and Easy to Order. No order to small. For those companies that are shopping for a better price, please use our easy to use navigation as a way to compare pricing to what you are currently receiving.
Calculation of Percent Blowdown for Cooling Tower Chemicals
Cycles for Cooling Towers and Condenser Water Systems
Cooling Tower ChemicalsThe purpose of a cooling tower or condenser system is to reuse water and reduce water usage. Determining the
conductivity set point of the water systemis important to maximumyour water reuse. Conductivity is the electrical
resistance measurement of the dissolved solids, suspended solids, and dissolved gases of the water and is expressed
in mico ohms (uomhs).
Corrosion inhibitors and scale prevention chemicals are used to maximize the number of cycles the water is used. The
definition of cycles is the number of times the water is reused in the water system.
For example, if the makeup water
to the cooling tower is 100 uomhs and your tower recirculating is 800 uomhs, your cycles are calculated as follows:
Cycles = Cooling Tower Recirculating Conductivity / Cooling TowerMake-up Water
For this Example: Cycles = 800 uomhs / 100 uomhs or 8
Percent blowdown for the tower is calculated the following way:
Percent Blowdown = ( 1 / Cycles) x100
For this Example: Precent Blowdown = (1/8) x100 = 12.5%
This means 12.5% of the water is being lost to blowdown.
Knowing your tower cycles is important for minimizing
water usage and reducing the amount of water lost to blowdown. Determining proper cylces or conductivity set point
is dependent on the water alkalinity and calcium. Every systemis unique.
Cooling Water Treatment
Cooling Water Treatment chemicals will minimize corrosion and scaling tendencies of your water system. Proper Cooling Water Treatment chemical selection is important. For additional questions on your Cooling Water Treatment needs, please contact use direct.
Need other Chemicals? Check out our other sites:
Propylene Glycol
Boiler Water Chemicals
Cooling Tower Chemicals
Motorized Ball Valves
Boiler Chemicals
Looking For Propylene Glycol, please visit our Propylene Glycol site and order direct.
Looking For Propylene Glycol, please visit our Vegetable Glycerin site and order direct.
Need a Pump. Check out Stenner Pump!. This is a great way to feed your chemicals! Please feel free to contact us today!
|
|
|